Mestek VERTICAL STEAM HOT WATER HEATERS Instrukcja Użytkownika

Przeglądaj online lub pobierz Instrukcja Użytkownika dla Grzejniki Mestek VERTICAL STEAM HOT WATER HEATERS. Mestek June 16, 2014 Instrukcja obsługi

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 145
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 0
Understanding Hydronic Systems
Mestek Institute, June 16, 2014
© Copyright 2014, J. Siegenthaler, all rights reserved.
The contents of this file shall not be copied or
transmitted in any form without written permission of
the author. All diagrams shown in this file on conceptual
and not intended as fully detailed installation drawings.
No warranty is made as the the suitability of any
drawings or data for a particular application.
Presented by: John Siegenthaler, P.E.
Przeglądanie stron 0
1 2 3 4 5 6 ... 144 145

Podsumowanie treści

Strona 1

Understanding Hydronic SystemsMestek Institute, June 16, 2014© Copyright 2014, J. Siegenthaler, all rights reserved. The contents of this file sha

Strona 2 - Today’s topics

common piping and !heat source have!HIGH FLOW RESISTANCEONONlarger circulatorsmaller circulatorP=22 psibackseated!flow checkP=17psicommon piping and !h

Strona 3 - How to achieve it

70758085909510010511070 60 50 40 30 20 10 0 -10supply water temperature (ºF) Outdoor temperature (ºF) reset linedesign load conditionno load condition

Strona 4 - Hydraulic Separation:

Determine the size of a buffer tank that will absorb 48,000 Btu/hr from the heat pump while increasing in temperature from 90 ºF to 110 ºF, during a h

Strona 5 - What is “COMMON PIPING?”

image courtesy of Mestek• Provide adequate space for air flow• Respect prevailing winds• In snowy climates, elevated above snow lineimage courtesy of R

Strona 6 - Very little head loss occurs!

• Provide adequate space for air flow• Minimize air flow interaction b/w adjacent HPsMultiple (staged) AWHPverticalrackmounting in alcove

Strona 7 - flow rate

Multiple (staged) AWHPStaged AWHP heat pumps for 20,000 square foot house.image courtesy of Foley Mechanical

Strona 8

Heat emitters for AWHP systems• They should operate at low supply water temperatures to enhance the thermal efficiency of the heat pump.Max suggested

Strona 9

Slab-on-grade floor heating02040600 10 20 30 40 50 60 70 80 90 100upward heat flux!(Btu/hr/ft2)Driving ∆T (Tw-Tr) (ºF)!Average water temp. - room air t

Strona 10 - 4 psi ∆P at 0 flow

Is radiant floor heating always the answer?“Barefoot friendly” floors...

Strona 11

Consider a 2,000 square foot well insulated home with a design heat loss of 18,000 Btu/hr. Assume that 90 percent of the floor area in this house is h

Strona 12 - Divide & Conquer:

A comparison of THERMAL MASS for several heat emitters:All heat emitters sized to provide 1000 Btu/hr at 110 ºF average water temperature, and 70 ºF r

Strona 13

space heating zoneslow flow resistance cast-iron boilerspace heating zoneshigh flow resistance mod/con boilerModern compact boilers have much higher flow

Strona 14

Low thermal mass allows the heat emitters to quickly respond to changing internal loadsNotice where the tubing is in this 6” heated concrete slab

Strona 15

Low temperature hydronic heat emitter options

Strona 16

Donʼt do this with ANY hydronic heat source!Heat transfer between the water and the upper floor surface is severely restricted!

Strona 17 - PARALLEL primary loop

Heat transfer between the water and the upper floor surface is severely restricted!Donʼt do this with ANY hydronic heat source!

Strona 18

What about standard fin-tube baseboard?Most fin-tube baseboard has been sized around boiler temperatures of 160 to 200 ºF. Much too high for good therm

Strona 19

Some low- temperature baseboard is now availableHydronic heat emitters options for low energy use housesStandard residential fin-tube baseboardMestek S

Strona 20

One of the fastest responding hydronic heat emittersFrom setback to almost steady state in 4 minutes…Panel RadiatorsHydronic heat emitters options

Strona 21 - Short / fat headers are GOOD!

• Adjust heat output for operation at lower water temperatures.Panel RadiatorsHydronic heat emitters options for low energy use housesRECOMMENDATION:

Strona 22

Site built radiant CEILINGS…Thermal image of radiant ceiling in operationWhere:Q = heat output of ceiling (Btu/hr/ft2)Twater = average water temperatu

Strona 23

Site built radiant CEILINGS…

Strona 24

circuit 2 circulator 2common!piping circulator 1circuit 1common!piping circulator 1circuit 1circuit 2 circulator 2common!piping Divide & Conquer:H

Strona 25

Thermal image of radiant ceiling in operationSite built radiant CEILINGS…

Strona 26 - “short / fat” headers

Site built radiant WALLS…

Strona 27 - • Hydraulic separation

Example Systems usingair-to-waterheat pumps

Strona 28

AWHP provides zoned heating + DHWmake up waterbuffer tankOUTSIDEINSIDEair to water heat pumpflow switchpressure regulated!variable speed circulatormani

Strona 29

(S1)RCsensors(S2)L1 N120 VACmain!switch(MS)HX - tank!circulatorL1 L2(R1)240 VACelectric!tankless!water!heaterHP - HX!circulator(R3-1)(P1)(P2)(P4)(R2-1

Strona 30 - (air & dirt removal)!

buffer tankOUTSIDEINSIDEair to water heat pumpflow switchoutdoor!temperature!sensoroutdoor!reset controllerpressure regulated!variable speed circulator

Strona 31

buffer tankOUTSIDEINSIDEair to water heat pumpflow switchoutdoor!temperature!sensoroutdoor!reset controllerpressure regulated!variable speed circulator

Strona 32 - 3. dirt separation

heat!exchangersensors in well(P3)(P4)(S2)zoned radiant ceiling panelsmanifold valve actuatorszone!thermostatsthermal trap(P2)outdoor!reset controller(

Strona 33 - Each case is governed by

OUTSIDEINSIDE2-stage!air to water heat pumpantifreeze!protected!circuitheat!exchangerDHWexpansion !tankmake up watersensors in wellthermostatically !c

Strona 34 - In this case only:!

AWHP provides excellent matching to solar PV system in net zero houses.• Future trends are toward “all electric” houses.• Heating loads are so small i

Strona 35 - ) supplied to the

• Simplifying system analysis• Preventing flow interferenceDivide & Conquer:

Strona 36

Chilled Beams:• All chilled beams must operate above dewpoint temperature of room!ceiling!warm air rising!cool air decending!dry, ventilation air inta

Strona 37 - flange connections

• reduces air flow requirements to those required for ventilation and latent cooling• reduces duct sizes• reduces blower size and reduced operation co

Strona 38

Radiant Ceiling Panels for heating & cooling1/2" drywall3/4" foil-faced polyisocyanurate foam stripsaluminum heat transfer platetube7/16

Strona 39

1/2" drywall3/4" foil-faced polyisocyanurate foam stripsaluminum heat transfer platetube7/16" oriented strand boardtop side insulationc

Strona 40

• low thermal mass• fast response• connect with “stab” fittingsSuspended ceiling panels (for heating & cooling)images courtesy of Zehnder

Strona 41

Suspended ceiling panels (for heating & cooling)installed in T-bar ceilingimages courtesy of Zehnderinstalled as self-supporting, suspended panels

Strona 42

Water temperature through radiant panel circuits must be maintained above dewpoint to avoid condensation.Chilled Water Cooling with Radiant Ceiling Pa

Strona 43

• Mixing valve operated by dewpoint controller maintain radiant panel supply temperature about 2-3 ºF above current room dewpoint temperature.• Latent

Strona 44

Same mixing valve and radiant panel can be used for heating, but with outdoor reset control logic (rather than dewpoint control logic).COOLING MODEHEA

Strona 45

• geothermal pre-conditioning of ventilation air• chilled water coil provide latent cooling (moisture removal)• Radiant panel(s) provide sensible cool

Strona 46

Primary / Secondary piping - where it all began... Dcloselyspacedteesmaximum 4xDflowprimary loopsecondary circuitsecondarycirculatorprimarycirculator

Strona 47 - Distribution Efficiency

1. Air to water heat pumps are available for hydronic heating, chilled water cooling, and domestic water heating.2. Both “self-contained” and “split s

Strona 48

Parting thoughts...1. Plan ahead...

Strona 49 - The present situation:

Parting thoughts...2. Keep it neat...

Strona 50 - Here’s another example…

Parting thoughts...3. Keep it simple...

Strona 51

Parting thoughts...4. Recognize opportunity...

Strona 52

http://www.spacepak.com/Thanks for attending today’s sessionwww.hydronicpros.com Please visit our website for more information Coming in October 201

Strona 53 - So what can you conclude

primary!circuitcirculator with integral flow-check (on supply)18"!min.swing-check !on returnswing check (or flow-check) valve (on return)underslung

Strona 54 - The North American hydronics

load!#1load!#2load!#3closely!spaced!tees!(typical)primary!circulatorsecondary!circuitsecondary!circuitsecondary!circuitsecondary circuitprimary!circui

Strona 55

Both series and parallel primary/secondary systems require a primary circulator.This adds to the installed cost of the system AND adds hundreds, even

Strona 56 - So is this!

An example of primary loop circulator operating cost:Consider a system that supplies 500,000 Btu/hr at design load. Flow in the primary loop is 50 gpm

Strona 57 - Efficiency =

Assuming electrical cost escalates at 4% per year the total operating cost over a 20-year design life is:This, combined with eliminating the multi-hun

Strona 58

Understanding Hydronic SystemsToday’s topics...• Hydraulic separation, what is it? & Why itʼs important• Distribution efficiency & low power pu

Strona 59

Question: What is the “ideal” header in a hydronic system?Answer: One that splits up the flow without creating head loss Think about a “copper basket

Strona 60 - = 0.4344 × f × ∆ P

So why donʼt we build headers like this???very low head loss!inside headerShort / fat headers are GOOD!Instead, we approximate the ideal header by mak

Strona 61

So whatʼs EXACTLY is a short / fat header???shortfatmax (design) flow rateselect pipe size that yields a flow velocity no higher than 2 feet per second

Strona 62

very low flow resistance!common piping!size headers for max flow velocity of 2 ft/seclow flow resistance heat!sourceThe “short / fat” headers hydraulical

Strona 63 - flow rate (gpm)

The “short / fat” headers hydraulically separate the distribution circulators from each other.closely spaced teesvery low flow resistance!common piping

Strona 64 - 0.4344 × f × ∆ P

multiple!boiler!controllerouside!sensorclosely!space!teeszone circulators!(w/ check valves)air!ventdrain!valvepurge!valves"short/fat" header

Strona 65

The “short / fat” headers hydraulically separate the distribution circulators from each other.buffer!tankvery low flow resistance!common piping!size he

Strona 66

Hydraulic Separation in “Micro-load” systems:The small insulated tank provides:• Thermal buffering• Hydraulic separation• Air separation and collectio

Strona 67

hydraulic separatorvery low flow resistance!common piping!high flow ! resistance boilersize headers for max flow velocity of 2 ft/secThe “short / fat” he

Strona 68 - ∆P as zone valves close

diameter = 1"flow velocity = 4 ft/secdiameter = 3"flow rate = 6.5 gpmflow velocity = 0.44 ft/secflow rate = 6.5 gpmarea = Aarea = 9Aalmost zero

Strona 69

Hydraulic SeparationWhat it is.Why itʼs important.How to achieve it.

Strona 70

drain valveair vent"STANDARD"!hydraulic !separatorWhat does the “coalescing media” do inside a hydraulic separator?The coalescing media crea

Strona 71

drain valveair venthigh performance!(low velocity zone)!dirt separatorhigh performance!(microbubble)!air separatordrain valveair ventWELDWELDdrain val

Strona 72

heating!load(s)boiler circuitdistribution systemair!separatorsediment!strainerclosely!spaced!teesheating!load(s)boiler circuitdistribution systemHydra

Strona 73

1. Flow in the distribution system is equal to the flow in the boiler circuit.2. Flow in the distribution system is greater than flow in the boiler circ

Strona 74

T4T3T2T1f1f2f3f4NOTE:=f1f3 (always!)f2f4=NOTE: (always!)In this case only:!T1T2T3T4==Case #1: Distribution flow equals boiler flow:Very little mixing oc

Strona 75

T4T3T2T1f1f2f3f4NOTE:=f1f3 (always!)f2f4=NOTE: (always!)Case #2: Distribution flow is greater than boiler flow:Mixing occurs within the hydraulic separa

Strona 76 - Circulators

Case #3: Distribution flow is less than boiler flow:T2=f4− f1( )T4+ f1( )T1f4⎛⎝⎜⎞⎠⎟The temperature returning to the boiler (T3) can be calculated with:W

Strona 77

Sizing of Hydraulic Separators:Hydraulic separators must be properly sized to provide proper hydraulic, air, and dirt separation. Excessively high flo

Strona 78

Typical European concepts for multiple mod/con installation:

Strona 79

Typical European concepts for multiple mod/con installation:

Strona 80

Hydraulic Separation:When 2 or more circulators are operating simultaneously in the same piping assembly, they try to “interfere” with each other.This

Strona 81 - “thermally

hydraulic!separatormultiple!boiler!controllersupply!temp.!sensoroutdoor!temperature!sensorto / from!loadsWhat did you notice in common on those last t

Strona 82 - • ECM-based pressure

Example of Hydro Separator Installation in New System:Magna Steel Corporation - ConnecticutPhotos courtesy of Peter Gasperini - Northeast Radiant

Strona 83 - Air-to-Water Heat Pumps:

Example of Hydro Separator Installation in Old System:Because hydraulic separators remove sediment fromsystems they’re ideal for applications where ne

Strona 84 - Why Water rather than air

Example of Hydro Separator Installation in Old System:Because hydraulic separators remove sediment from systems theyʼre ideal for applications where n

Strona 85 - 3/4" tube

existing cast-iron radiators (converted from steam)existing pipingmod/con boiler!w/ compact heat exchangersupply!temperature!sensorECM!pressure!regula

Strona 86 - Basic heat pump operation

fluid feederearth loop circuitspurging!valvespurgevariable-speed!pressure-regulated!circulatorgeothermal manifoldshydro!separatorto / from!other heat p

Strona 87

Whatʼs wrong with these installations?Answer: There is nothing to drive flow through the circuit on the left side of separator. The closely spaced tee

Strona 88 - COOLING!

Distribution Efficiency& Low Power Pumping...00.050.10.150.20.250 2 4 6 8 10 12 14 16 180481216wire-to-water efficiency (decimal %)flow rate (gpm)hea

Strona 89 - Refrigeration cycle in AWHP

The North American Hydronics market has many “high efficiency” boilersIn the right applications these boilers have efficiencies in the 95+ range:It may

Strona 90 - (antifreeze in outside unit)

The present situation:What draws your attention in the photo below?If all these circulators operate simultaneously (at design load) the electrical dem

Strona 91

What is “COMMON PIPING?”The degree to which two or more operating circulators interact with each other depends on the head loss of the common piping.T

Strona 92 - Heating performance:

Here’s another example…Great “craftsmanship” - Wrong “concept”

Strona 93

Here’s another (award winning) example…

Strona 94 - Cooling performance:

If you run out of wall space consider this installation technique…Notice the installer left provisions for additional circulators.

Strona 95

So what can you conclude from these photos?Perhaps that it’s GOOD to be in the circulator business these days!

Strona 96 - AWHP + auxiliary heating

You might also conclude that…The North American hydronics industry tends to “overpump” its systems!

Strona 97 - flow switches

Just to be fair to the pump guys – there is such a thing as overzoning with zone valves…

Strona 98 - <= 5ºF

Although as an industry we pride ourselves on ultra high efficiency and “eco-friendly” heat sources, we…Must look beyond the efficiency of only the heat

Strona 99

Defining DISTRIBUTION EFFICIENCYEfficiency = desired OUTPUT quantitynecessary INPUT quantityDistribution efficiency for a space heating system.Consider

Strona 100 - Using a buffer tank with AWHP

So is a distribution efficiency of 353 Btu/hr/watt good or bad?To answer this you need something to compare it to.Suppose a furnace blower operates at

Strona 101

Room for Improvement…A few years ago I inspected a malfunctioning hydronic heating system in a 10,000 square foot house that contained 40 circulators.

Strona 102 - Multiple (staged) AWHP

Very little head loss occurs!in this portion of the circuits.common piping circulator 1circuit 1circuit 2 circulator 2When the head loss of the common

Strona 103

Water Watts… It’s hard to say if the wattage of past or current generation circulators is “where it needs to be” without knowing the mechanical power

Strona 104

Example: How much mechanical power is necessary to sustain a flow of 180 ºF water flows at 5 gpm through a circuit of 3/4” copper tubing having an equi

Strona 105

The ratio of the mechanical wattage the impeller imparts to the water divided by the electrical input wattage to operate the motor is called wire-to-w

Strona 106 - Slab-on-grade floor heating

00.050.10.150.20.250 2 4 6 8 10 12 14 16 180481216wire-to-water efficiency (decimal %)flow rate (gpm)head added (feet)pump curvewire-to-water efficiencym

Strona 107 - “Barefoot friendly” floors

The electrical wattage needed by the circulator is:we=0.4344 × f × ∆ Pnw/wA current-generation wet-rotor circulator has a maximum wire-to-water efficie

Strona 108 - floor heating promote

Consider that a flow of 5 gpm in a circuit with a 20 ºF temperature drop is moving about 50,000 Btu/hr, and the electrical power to “run the conveyor b

Strona 109

This graph shows the relationship between system flow rate vs. operating hours for a typical Northern climate.Recognizing that partial flow is common, c

Strona 110

What happens when a zone valve closes?

Strona 111

Applying ∆P CirculatorsFlat pump curves produce less of the undesirable increase in ∆P as zone valves close.

Strona 112

What would be the ideal pump curve for a hydronic system using valve based zoning?zone valvesDHWCWAnswer: a perfectly flat pump curveA perfectly flat p

Strona 113

Very little head loss occurs!in this portion of the circuits.common piping circulator 1circuit 1circuit 2 circulator 2Assume that circulator 1 is oper

Strona 114

Approximating a flat pump curve with ∆P bypass valveA ∆P bypass valve helps limit changes in differential pressure, but does so “parasitically” by thro

Strona 115 - Synergy

Approximating a flat pump curve with ∆P bypass valveBy varying the speed of the circulator it is possible to produce the same “net” effect as would be

Strona 116 - Panel Radiators

PROPORTIONAL DIFFERENTIAL PRESSURE CONTROLThis method is best for systems where the heat source and/or “mains” piping leading to the load circuits dis

Strona 117

How does a ECM Circulator work?

Strona 118 - Site built radiant CEILINGS…

Single or multi-speed wet-rotor circulators like those commonly used in North America would be rated “D” or “E” on this scale.All these circulators ra

Strona 119

Small ECM circulators now available in North AmericaGrundfos Alpha: Provides constant and proportional differential pressure and three fixed speed set

Strona 120

Grundfos MAGNAWilo STRATOS circulatorsLarger ECM circulators now available in USTaco ViridianHeads to 45 feet, flows to 345 gpmpower inputs to 1600 wat

Strona 121 - Site built radiant WALLS…

Savings in electrical energy are 60 to 80 percent relative to a fixed speed circulator of equal peak performance in the same application.Computer model

Strona 122 - Example Systems

TRVTRVTRVTRVTRVTRVthermal storage tankthermostatic radiator valves!on each panel radiatorpressure-regulated!variable speed circulator1/2" PEX or

Strona 123 - flow switch

Homerun systems allow several methods of zoning.Another approach is to install a thermostatic radiator valve (TRV) on each heat emitter.One approach i

Strona 124

Very little head loss occurs!in this portion of the circuits.common piping circulator 1circuit 1circuit 2 circulator 2Imagine a hypothetical situation

Strona 125 - HEATING MODE

NON-ELECTRIC THERMOSTATIC RADIATOR VALVE: operatorvalve body

Strona 126 - COOLING MODE

thermostatic radiator valves are easy to use...manual setback dog reset controldogs are “thermally discriminating.”

Strona 127

The modern way to install fin-tube baseboard:• Thermostatic radiator valve on each baseboard• ECM-based pressure-regulated circulator.

Strona 128

Air-to-Water Heat Pumps:OUTSIDEINSIDEair to water heat pump

Strona 129

Why Water rather than air

Strona 130 - Chilled Beams:

14" x 8" ductthis cut would destroy the load-carrying ability of the floor joists2 x 12 joist3/4" tube Water is vastly superior to air f

Strona 131

compressorthermal expansion valve!(TXV)condenserevaporatorSOURCE!mediaLOAD!media1234refrigerant flowhigh temperature!high pressure!VAPORmedium temperat

Strona 132

Basic heat pump operationcompressorthermal expansion valve!(TXV)condenserevaporatorlow !temperature!heat!absorbed!from source!(Q1)higher !temperature!

Strona 133 - = 8.6º F

compressorthermal expansion valve!(TXV)condenserevaporatorreversing!valvelow !temperature!heat!absorbedhigher !temperature!heat!dissipatedHEATING!MODE

Strona 134 - • connect with “stab” fittings

Refrigeration cycle in AWHPevaporatorTXVRVcomp.air-to-water!heat pump(in cooling mode)circulatorcondenserfanoutside!airoutside!airheat!from!buildingco

Strona 135

The higher the flow resistance of the common piping, the more each circulator will “influence” flow in the other circuit (e.g. the lower the hydraulic se

Strona 136

Self-contained air-to-water heat pumpswarmer climate application(water in outside unit)colder climate application(antifreeze in outside unit)image cou

Strona 137 - Chilled Water Cooling

One comparison with Geothermal w/w heat pump:Example house: 36,000 BTU/hr design load at 70ºF inside & 0 ºF outsideLocation: Syracuse, NY (6720 h

Strona 138

20000300004000050000600007000080000-10 0 10 20 30 40 50 60 70Heating capacity (Btu/hr) Outdoor air temperature (ºF) leaving load water temp = 86 ºF

Strona 139 - HRV or ERV Ventilation

Heating performance:Anything that reduces the “temperature lift” increases both the heating capacity and COP of the heat pump.outside airload watertem

Strona 140 - Summary:

Cooling capacityIncreases with:a. lower outdoor temperatureb. Higher chilled water temperatureEERIncreases with:a. lower outdoor temperatureb. higher

Strona 141 - 1. Plan ahead

Anything that decreases the temperature liftʼ increases both the cooling capacity and EER of the heat pump.outside airtemperature!"lift"!(le

Strona 142 - 2. Keep it neat

AWHP + auxiliary heating050001000015000200002500030000350004000070 60 50 40 30 20 10 0Load or heat pump output (Btu/hr) outdoor temperature (ºF) heat

Strona 143 - 3. Keep it simple

Flow switches protect the heat pumpflow switchesAn internal or external flow switch turns off the refrigeration cycle if water flow through the heat pump

Strona 144 - 4. Recognize opportunity

Heat exchangers between heat pump and distribution systemIF a heat exchanger is required between heat pump and storage (due to requirement to keep hea

Strona 145 - Coming in October 2014

Low voltage interfacing with AWHPRYOC24 VACcompressorreversing valvecommonRYOC24 VACcompressorreversing valvecommon(RA)heat!demand(RA-1)cool!demandrel

Komentarze do niniejszej Instrukcji

Brak uwag